Need help connecting the WIB8000 network module. Has anyone worked with STULZ equipment?

Are there air conditioning system integrators on the portal?
I had difficulties with connecting the WIB 8000 module via the 485 bus, which allows me to receive data from STULZ microclimate units over the network.
There is a manual on it, in accordance with which I made the connection ( www.stulz-ats.com/repository/F5ABD290/C8000_WIB_ST... At the moment, another device is connected to ports 13.14 of the 7000AT controller, and the controllers 7000 IOC, and accordingly 7000AT sees them normally.If you do as according to the instructions and connect the wib8000 module to ports 13-14 (having disconnected the old device) and try to auto-search through the menu, the result will be zero.
If you manually create a 7000AT module, then it is not displayed in the view on the bus, but the detected devices "1" appear in the search. Terminating resistors are installed, global addresses on devices are set as follows: AT - 1, IOC (first) - 2, IOC (second) -3.
As far as I understand, the address is not set on the WIB module itself, because I didn’t find it anywhere in the settings, and it’s not indicated in the description.