What is the optimal temperature and humidity in the data center?
What is the optimal temperature (maximum and minimum) and humidity should be in the data center?
Please share your experience, who works and worked in data centers
Answer the question
In order to leave comments, you need to log in
I found the answer myself.
In accordance with the document SP–3-0092: (TIA-942 Standard, edition
7.0, February 2005) “Telecommunications infrastructure of
Data Processing Centers” clause 5.3.5.3. “Environmental operating parameters”
(excerpt from the document)
“5.3.5.3. Environmental operating parameters
- psychrometer dry bulb temperature: 20º C (68º F) to 25º C
(77º F);
- relative humidity: from 40% to 50%;
- dew point: no more than 21º C (69.8º F);
- rate of change: no more than 5º C (9º F) per hour;